Why is continuous circulation important in a PW distribution loop?
Continuous circulation is essential because purified water is highly susceptible to microbial contamination when stagnant. A well-designed PW loop maintains constant flow, pressure, and temperature—typically with a minimum velocity of 1–1.5 m/s—to prevent biofilm formation and maintain sanitary conditions. Many systems use hot water (≥65°C) or chemical sanitization to...